Worked example — default entered values
Entered margin: 20% — compare the result with a verified continuous rating.
Load 1: 1.6 kW ÷ PF 0.9 = 1.778 kVA · Load 2: 0.7 kW ÷ PF 0.8 = 0.875 kVA · Entered margin: 20%
Entered kW is electrical input power and all entered loads operate concurrently.
Each entered power factor applies at the expected operating point.
The entered margin is a planning assumption, not a regulatory value.
Starting demand, harmonics, voltage drop, ambient derating and duty cycle are not modelled.
Compare against a verified continuous rating. Starting/inrush demand, duty or intermittent rating, plug/input, individual outlet current and manufacturer instructions can govern. Supplier, manufacturer or competent-person confirmation is required.
PLANNING ESTIMATE. Compare against the verified continuous rating. Starting/inrush demand, duty or intermittent rating, plug/input, individual outlet current and manufacturer instructions can govern. Supplier, manufacturer or competent-person confirmation is required.